JL-206 NEMA interface Twist-lock Photocell Light Sensor

JL-206 Twsit lock analog electronic light control switch series products are applicable to independently control street lighting, garden lighting, passage lighting, porch lighting and park lighting according to the ambient natural lighting level.

This series of products has designed a microprocessor circuit with infrared filter optical transistor, and is equipped with a surge arrester (MOV). In addition, the preset 5-20 second time delay control function can avoid redundant operation caused by spotlight or lightning at night.

The long-life version can maintain constant and reliable characteristics. The relay can have more than 10000 working life cycles. When a double-layer protective shell is installed, it can provide a longer working life for JL-206. HP version can provide higher load.

This series of products provides three lock terminals, which meet the requirements of ANSI C136.10 and ANSI/UL773 standard for plug-in and rotary lock optical controllers for area lighting.

JL-206C_longjoin
JL-206C_04
Product feature
·ANSI C136.10 twist lock
·Wide voltage
·Inverse illuminance
·Fully customizable
·Built-in surge protection
·Infrared filter phototransistor
·Midnight light
·Zero crossing protection
·Optional failure mode on/off
·UV resistant housing
·Support FCC class A

Item JL-206C5 JL-206C4 JL-206C5HP JL-206C4HP
Rated Voltage 120-277VAC
Rated Frequcy 50/60Hz
Work Temperatue -40℃-70℃
Relative Humidity 96%
Rated Loading 1000W Tungsten;1800VA Ballast;8A@120VAC 5A@208-277VAC e-Ballast 1800W@120VAC 2000W Tungsten;
1800VA@120VAC
Ballast;2000VA@208-277VAC
Power Consumption 0.5W Max 0.9 Max
Double Cover Option
IP Rating IP54/IP65/IP66
Fail Mode Fail on/Fail off
Cross Zero option
FCC Optioan -
Certificate UL,CE,ROHS

____________________________________________________________________

Item JL-206E5 JL-206E4 JL-206F4 JL-206F5
Rated Voltage 347VAC 480VAC
Rated Frequcy 50/60Hz
Work Temperatue -40℃-70℃
Relative Humidity 96%
Rated Loading 1800W Tungsten;1800VA Ballast;5A e-Ballast 1800W Tungsten;
1800VA Ballast
Power Consumption 0.5W Max
Double Cover Option
IP Rating IP54/IP65/IP66
Fail Mode Fail on/Fail off
Cross Zero -
FCC - -
Certificate UL,CE,ROHS

Installation Instructions

JL-206C_03

*Disconnect the power supply.
*Connect the socket according to the figure below.
*Push the photoelectric controller up and turn it clockwise to lock it in the socket.
*If necessary, adjust the socket position to ensure that the light sensing port points to the north as shown in the triangle on the top of the light controller.

 

Initial testing

*It is normal for the Photocontrol to take few minutes to turn off when first installed.
*To test “turn on” during daytime, cover its eye with opaque material.
*Do not cover with finger because light traveling through fingers may be great enough to keep the Photocontrol off.
**photo control test will take approximately 2 minutes.
* Operation of this Photocontrol is not affected by weather, moisture or temperature changes.

Product Code Table
JL-206C_01

1: C = 120-277VAC
E = 347VAC
F = 480VAC
2:5=light on
4=light off
3: F12 = MOV,110J/3500A
F15 = MOV,235J/5000A
F23 = MOV,460J/10000A
F25 = MOV,546J/10000A
F40 = MOV,640J/ 40000A
M4K = MOV,4KV Surge

D6K = R/C,6KV Surge

R2W = R/C,20KV Surge

A2W = A/D,20KV Surge

4: F=Conforming to the requirements of FCC electromagnetic interference specification, Class B

N=FCC compliance not verified

5: HP = Hi-Power 20Amp

S = Standard 10Amp

6: P=UV stabilized polypropylene

C=UV stabilized polycarbonate
K=PP inner shell+PC shell

7: F=blue D=green H=black

K=gray optional

8: IP65=elastomer ring+silicone outer seal

IP54=Electronically associated foam washer

IP66=elastomer ring+silicone inner and outer sealing

IP67=silicone ring+silicone inner and outer sealing (including copper pin)
9: Illumination
10: Lamp on delay (seconds)
11: Illumination after turning off the light
12: lamp off delay (seconds)
13: Optional mid-night dimming (hours)
14: Z=optional zero-crossing control technology+long life
N=None

 