Testsample: photocontroller(JL-207C), receptaculum rotatum (JL-240TLXA)
Item No: JL-240TLXA, JL-207C .
Rating: 480VAC, 15AMP
Rogatus test: IPX5 test
Test Methodus (signa): secundum huius postulationem et refer ad IEC 60529+A1.1999+A2: 2013/EN 60529:1991+A1:200+A2:2013 clasuse 14.2.5
TestisLabortivum: SGS-CSTC Signa Technical Services (Shanghai) Co., Ltd.
Dies test deductus est: 2017-3-30 2017-4-1
Date ex specimen receptionis: 2017-03-30
Tet consequuntur: pass
ConclusionEt summitto sample IPX5 exigentias parere "
Effectum deducendi conditione
Expertus factus est saeptum ab omnibus practicis directionibus spargendo cum aquae rivo e norma testiculi colliculi ut infra experimentum missionis figurae.
Conditio servanda haec est:
diametri colli -interni: 6.3 mm longi;
- traditio rate: 12.5 L/min +-5%;
-water pressura: ad accommodandum ad consequi praefinitum partus rate;
-cor amnis substantialis: circulus circiter 40 mm diametri ad 2.5 m distantium a COLLUM;
-test durationem per quadratum metri clausurae superficiei areae asperso probabile: 1 min;
-minute test durabile: 3 min;
-distantia a COLLUM usque ad superficiem clausurae: inter 2.5 m et 3 m.
Observationes:
Excessus aquae intra clausuram in fine test iPX5 non inventae sunt.
Intellectualis proprietas legalis est personae: Longjoin.
Post tempus: Iun-22-2020